List of parameters
Parameter
1-79
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Note:
For the automatic calculation, the pole pair number is set to the value of 2 if the rated speed or the rated frequency
is zero.
Description:
Sets the motor pole pair number.
p0314 = 1: 2-pole motor
r0314 = 2: 4-pole motor, etc.
Dependency:
For p0314 = 0, the pole pair number is automatically calculated from the rated frequency (p0310) and the rated
speed (p0311) and displayed in r0313.
Notice:
If p0314 is changed during quick commissioning (p0010 = 1), the maximum speed p1082, which is also associated
with quick commissioning, is pre-assigned accordingly. This is not the case when commissioning the motor (p0010
= 3).
For induction motors, the value need only be input if the rated data of a generator is entered therefore resulting in a
negative rated slip. In this case, the number of pole pairs in r0313 is too low by 1 and must be manually corrected.
Description:
Sets the torque constant of the synchronous motor.
p0316 = 0: The torque constant is calculated from the motor data.
p0316 > 0: The selected value is used as torque constant.
Dependency:
Refer to: r0334, r1937
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
This parameter is not used for induction motors (p0300 = 1xx).
Description:
Sets the stall current for synchronous motors (p0300 = 2xx).
Caution:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected. Infor-
mation in p0300 should be carefully observed when removing write protection.
Note:
The parameter is used for the I2t monitoring of the motor (refer to p0611).
This parameter is not used for induction motors (p0300 = 1xx).
p0314[0...n]
Motor pole pair number / Mot pole pair No.
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(1, 3)
Calculated:
-
Access level:
1
Data type:
Unsigned16
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 4000
0
p0316[0...n]
Motor torque constant / Mot kT
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(1, 3), U, T
Calculated:
-
Access level:
1
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor
Units group:
28_1
Unit selection:
p0100
Not for motor type:
ASM, REL, FEM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Nm/A]
400.00 [Nm/A]
0.00 [Nm/A]
p0318[0...n]
Motor stall current / Mot I_standstill
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
C2(3)
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
8017
P-Group:
Motor
Units group:
-
Unit selection:
-
Not for motor type:
ASM, REL, FEM
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Arms]
10000.00 [Arms]
0.00 [Arms]