Parameter
List of parameters
1-282
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Displays diagnostics information for the pole position identification routine (PollD).
Dependency:
Refer to: p0325, p0329, p1980, p1981, p1982, p1983, r1984, r1985, r1986, r1987, p1990, p1993, p1994, p1995,
p1996, p1997
Note:
PolID: Pole position identification
Description:
Sets the current when executing the motion-based pole position identification.
Dependency:
Refer to: p1980, p1981, p1982, p1983, r1984, r1985, r1986, r1987, p1990, r1992, p1994, p1995, p1996, p1997
Note:
PolID mot: Motion-based pole position identification
Description:
Sets the rise time of the current when executing the motion-based pole position identification.
Dependency:
Refer to: p1980, p1981, p1982, p1983, r1984, r1985, r1986, r1987, p1990, r1992, p1993, p1995, p1996, p1997
Note:
PolID mot: Motion-based pole position identification
r1992
PolID diagnostics / PolID diag
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Critical encoder fault occurred
Yes
No
-
02
Encoder parking active
Yes
No
-
05
Encoder fault Class 1
Yes
No
-
06
Encoder fault Class 2
Yes
No
-
07
Pole position identification for encoder car-
ried out
Yes
No
-
08
Fine synchronization carried out
Yes
No
-
09
Coarse synchronization carried out
Yes
No
-
10
Commutation information available
Yes
No
-
11
Speed information available
Yes
No
-
12
Position information available
Yes
No
-
15
Zero mark passed
Yes
No
-
p1993[0...n]
PolID motion-based current / PolID I mot_bas
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
CALC_MOD_EQU
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor identification
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [Arms]
20000.00 [Arms]
0.00 [Arms]
p1994[0...n]
PolID motion-based rise time / PolID T mot_bas
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
MDS, p0130
Func. diagram:
-
P-Group:
Motor identification
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 [ms]
2500 [ms]
100 [ms]