List of faults and alarms
Faults and alarms
3-1045
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Remedy:
Set the speed controller clock cycles the same (p0115[1]).
Note:
PB: PROFIBUS
PN: PROFINET
A01932
PB/PN clock cycle synchronization missing for DSC
Message value:
-
Drive object:
SERVO_S110-CAN, SERVO_S110-DP, SERVO_S110-PN
Reaction:
NONE
Acknowledge:
NONE
Cause:
There is no clock synchronization or clock synchronous sign of life and DSC is selected.
Note:
DSC: Dynamic Servo Control
See also: p0922, p1190, p1191
Remedy:
Set clock synchronization across the bus configuration and transfer clock synchronous sign-of-life.
See also: r2064 (PROFIdrive diagnostics clock synchronous mode)
A01940
PB/PN clock cycle synchronism not reached
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram. It was not possible to synchronize to the clock cycle specified by the master.
- the master does not send a clock synchronous global control telegram although clock synchronous operation was
selected when configuring the bus.
- the master is using another clock synchronous DP clock cycle than was transferred to the slave in the parameter-
izing telegram.
- at least one drive object has a pulse enable (not controlled from PROFIBUS/PROFINET either).
Remedy:
- check the master application and bus configuration.
- check the consistency between the clock cycle input when configuring the slave and clock cycle setting at the mas-
ter.
- check that no drive object has a pulse enable. Only enable the pulses after synchronizing the PROFIBUS/PROFI-
NET drives.
Note:
PB: PROFIBUS
PN: PROFINET
A01941
PB/PN clock cycle signal missing when establishing bus communication
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram. The global control telegram for synchronization is not being received.
Remedy:
Check the master application and bus configuration.
Note:
PB: PROFIBUS
PN: PROFINET
A01943
PB/PN clock cycle signal error when establishing bus communication
Message value:
-
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The bus is in the data exchange state and clock synchronous operation has been selected using the parameterizing
telegram. The global control telegram for synchronization is being irregularly received.
-.the master is sending an irregular global control telegram.