List of parameters
Parameter
1-237
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Re bit 02:
The current controller adaptation (p0391 ... p0393) is only calculated when the bit is set.
Description:
Sets the speed to change over between operation with and without an encoder.
Above this speed, the drive system is automatically operated in encoderless mode.
Notice:
General conditions for encoderless operation can be found in the following literature:
SINAMICS S120 Function Manual Drive Functions
Note:
The changeover speed applies when changing over between operation with and without encoder.
With p1404 > 0, the effective changeover speed is limited to values greater than or equal to p1755 in order to avoid
controlled operation.
Separate speed controllers should be set when operating with and without encoder.
- Operation with encoder: p1460 (Kp), p1462 (Tn), p1461, p1463, p1457, p1458 (speed controller adaptation)
- Operation without encoder: p1470 (Kp), p1472 (Tn)
For encoderless operation (p1404 = 0 or p1300 = 20), the following applies:
- The condition must be fulfilled: p1800 >= n / (2 * p0115[0]), n = 1, 2, ...
- For motors with a small power rating (< 300 W) we recommend to set n >= 2.
Description:
Displays the control word of the speed controller.
Description:
Displays the status word of the speed controller.
p1404[0...n]
Encoderless operation changeover speed / Encoderl op n_chg
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
1590, 5060
P-Group:
Closed-loop control
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0.00 [rpm]
210000.00 [rpm]
210000.00 [rpm]
r1406.8...12
CO/BO: Control word speed controller / STW n_ctrl
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
1530, 2520
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
08
Travel to fixed stop active
Yes
No
-
12
Torque control active
Yes
No
-
r1407.0...13
CO/BO: Status word speed controller / ZSW n_ctrl
SERVO_S110-CAN,
SERVO_S110-DP,
SERVO_S110-PN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned32
Dynamic index:
-
Func. diagram:
1530, 2522
P-Group:
Closed-loop control
Units group:
-
Unit selection:
-
Not for motor type:
REL
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
U/f control active
Yes
No
-
01
Encoderless operation active
Yes
No
-
02
Torque control active
Yes
No
8010
04
Speed setpoint from DSC
Yes
No
2522
05
Speed controller I component frozen
Yes
No
-
06
Speed controller I component set
Yes
No
-
07
Torque limit reached
Yes
No
5610
08
Upper torque limit active
Yes
No
5610
09
Lower torque limit active
Yes
No
5610