List of parameters
Parameter
1-203
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets skip speed 3.
Dependency:
Refer to: p1091, p1092, p1094, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description:
Sets skip speed 4.
Dependency:
Refer to: p1091, p1092, p1093, p1101
Notice:
Skip bandwidths can also become ineffective as a result of the downstream limits in the setpoint channel.
Description:
Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency:
Refer to: p1091, p1092, p1093, p1094
Note:
The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint speeds between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint speed coming from below, the following applies:
r1170 < 580 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 580 [rpm]
For a setpoint speed coming from above, the following applies:
r1170 > 620 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 620 [rpm]
p1093[0...n]
Skip speed 3 / n_skip 3
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
3050
P-Group:
Setpoints
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1094[0...n]
Skip speed 4 / n_skip 4
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
3050
P-Group:
Setpoints
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
p1101[0...n]
Skip speed bandwidth / n_skip bandwidth
SERVO_S110-CAN
(Extended set),
SERVO_S110-DP
(Extended set),
SERVO_S110-PN
(Extended set)
Can be changed:
U, T
Calculated:
-
Access level:
3
Data type:
FloatingPoint32
Dynamic index:
DDS, p0180
Func. diagram:
3050
P-Group:
Setpoints
Units group:
3_1
Unit selection:
p0505
Not for motor type:
-
Scaling:
p2000
Expert list:
1
Min Max
Factory
setting
0.000 [rpm]
210000.000 [rpm]
0.000 [rpm]
Содержание SINAMICS S110
Страница 1: ...s SINAMICS S110 List Manual 06 2012 SINAMICS ...
Страница 2: ......
Страница 1272: ...List of abbreviations B 1272 Siemens AG 2012 All Rights Reserved SINAMICS S110 List Manual LH7 06 2012 6SL3097 4AP10 0BP3 ...
Страница 1286: ...Index C 1286 Siemens AG 2012 All Rights Reserved SINAMICS S110 List Manual LH7 06 2012 6SL3097 4AP10 0BP3 ...
Страница 1287: ......