List of parameters
Parameter
1-523
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3
Description:
Sets the automatic BICO interconnection of the CANopen control word.
Value:
0:
No interconn
1:
Interconnection
Dependency:
Refer to: r2050, r2090, r2091, r2092, r2093, r8750, r8795
Note:
The following BICO interconnections are automatically established if the CANopen control word is mapped at one
of the locations x = 0 ... 3 in the receive process data buffer.
For SINAMICS S120 with CBC10, the PZD interface IF2 is used:
BI: p0840.0 = r889x.0
BI: p0844.0 = r889x.1
BI: p0848.0 = r889x.2
BI: p0852.0 = r889x.3
BI: p2103.0 = r889x.7
For SINAMICS S110, the PZD interface IF1 is used:
BI: p0840.0 = r209x.0
BI: p0844.0 = r209x.1
BI: p0848.0 = r209x.2
BI: p0852.0 = r209x.3
BI: p2103.0 = r209x.7
The write access is rejected if a CANopen control word is not mapped at one of these locations.
This also causes the project download of the commissioning software to be canceled.
Description:
Access to the CANopen control word using SDO transfer.
Dependency:
Refer to: p8790
Note:
Corresponds to the CANopen object 6040 hex + 800 hex * x (x: Drive number 0 ... 7).
p8790
CAN control word - auto interconnection / STW interc auto
SERVO_S110-CAN
Can be changed:
C1(3), T
Calculated:
-
Access level:
3
Data type:
Integer16
Dynamic index:
-
Func. diagram:
-
P-Group:
Communications
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
0 1
0
r8795
CAN control word / Control word
SERVO_S110-CAN
Can be changed:
-
Calculated:
-
Access level:
3
Data type:
Unsigned16
Dynamic index:
-
Func. diagram:
-
P-Group:
-
Units group:
-
Unit selection:
-
Not for motor type:
-
Scaling:
-
Expert list:
1
Min Max
Factory
setting
- -
-
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
Do not activate coast down
Yes
No
-
02
Do not activate a Quick Stop
Yes
No
-
03
Operation enable
Yes
No
-
07
Acknowledge fault
Yes
No
-
11
Freely interconn
High
Low
-
12
Freely interconn
High
Low
-
13
Freely interconn
High
Low
-
14
Freely interconn
High
Low
-
15
Freely interconn
High
Low
-