15
ENGLISH
25
4-2.
Recommended Wire Length and Wire Diameter for Power Supply System
Outdoor unit
(A) Power supply
Time delay fuse or
circuit capacity
Wire size
Max. length
8 HP
4 mm²
57 m
25 A
10 HP
4 mm²
40 m
30 A
or
(A) Power supply
Time delay fuse or
circuit capacity
Wire size
Max. length
6 mm²
86 m
35 A
6 mm²
60 m
35 A
Indoor unit
Type
(B) Power supply
Time delay fuse
or
circuit capacity
Type
(B) Power supply
Time delay fuse
or
circuit capacity
Minimum 2 mm²
2.5 mm²
M
inimum 2 mm²
2.5 mm²
K2
Max. 150 m
—
15 A
D
1
—
Max. 130 m
10 – 16 A
Y2
Max. 130 m
—
15 A
L1
—
Max. 130 m
10 – 16 A
K1
—
M
ax. 150 m
10 – 16 A
M
1
—
Max. 130 m
10 – 16 A
U1
—
M
ax. 130 m
10 – 16 A
P
1
—
Max. 130 m
10 – 16 A
F2
—
M
ax. 130 m
10 – 16 A
R
1
—
Max. 130 m
10 – 16 A
T2
—
M
ax. 130 m
10 – 16 A
E
2
—
Max. 30 m
10 – 16 A
Control wiring
(C) Inter-unit (between outdoor and indoor units) control wiring
0.75 mm² (AWG #18)
Use shielded wiring*
or
2.0 mm² (AWG #14)
Use shielded wiring*
Max. 1,000 m
M
ax. 2,000 m
(D) Remote control wiring
0.75 mm² (AWG #18)
Max. 500 m
NOTE
* With ring-type wire terminal
(E) Control wiring for group control
0.75 mm² (AWG #18)
Max. 200 m (Total)
00̲280220̲2WAY̲Eng.indb 25
2016/06/09 18:11:03
26
4-3.
Wiring System Diagram
U2
U1
R2
R1
L
N
R2
R1
R2
R1
R2
R1
2
1
2
1
U2
U1
L
N
U2
U1
L
N
U2
U1
L
N
2
1
2
1
2
1
D
E
C
B
L
N
L
N
L
N
L
N
2
1
B
B
B
C
D
D
C
A
L1 L2 L3 N
C
L1
L2
U1
U2
L3
N
WHT BLK
WHT BLK
WHT BLK
NOTE
(1)
See the section “4-2. Recommended Wire Length and Wire
Diameter for Power Supply System” for the explanation of
“A”, “B”, “C”, “D” and “E” in the above diagram.
(2)
The basic connection diagram of the indoor unit shows the
6P terminal board, so the terminal boards in your equipment
may differ from the diagram.
(3)
Refrigerant Circuit (R.C.) address should be set before
turning the power on.
(4)
Regarding the R.C. address setting, it can be executed by
remote controller automatically. See the section “7-4. Auto
Address Setting”.
4P terminal board
Power supply
2P terminal board
Inter-unit control wiring
Outdoor unit
Power supply
220/230/240V ~ 50/60 Hz
Ground
Ground
Ground
Ground
Ground
Ground
Ground
Ground
Indoor unit (No. 1)
Outdoor unit INV unit
Power supply
380/400/415V, 3 N~, 50Hz
Indoor unit (No. 2)
Indoor unit (No. 3)
Indoor unit (No. n)
Remote controller
Power supply
220/230/240V ~ 50/60 Hz
Ground
Remote controller
Power supply
220/230/240V ~ 50/60 Hz
Ground
Group control:
Power supply
220/230/240V ~ 50/60 Hz
Ground
Remote controller
00̲280220̲2WAY̲Eng.indb 26
2016/06/09 18:11:04
00̲280434̲Mini̲VRF̲Mentsuke.indb 15
00̲280434̲Mini̲VRF̲Mentsuke.indb 15
2016/06/16 11:37:39
2016/06/16 11:37:39