A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
337
Para
me
te
r Lis
t
A
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
H4-01
Multi-Function
Analog Output
Terminal AM)
Selects the data to be output through multi-
function analog output terminal AM.
Set the desired monitor parameter to the digits
available in U -
. For example, enter
“103” for U1-03.
When using this terminal in through mode or
when not using it at all, set “000” or “031”.
000 to
999
102 A A A
41D
H4-02
Multi-Function
Analog Output
Terminal AM Gain
Sets terminal AM output level when selected
monitor is at 100%.
Maximum output voltage is 10 V.
-999.9 to
999.9
100.0
%
S S S
41E
H4-03
Multi-Function
Analog Output
Terminal AM Gain
Sets terminal AM output level when selected
monitor is at 0%.
-999.9 to
999.9
0.0% A A A
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
H5-01
Drive Node Address
Selects drive station node number (address) for
MEMOBUS/Modbus terminals R+, R-, S+, S-.
Cycle power for the setting to take effect.
0 to
20 H
1F
A A A
425
H5-02
Communication Speed
Selection
Selects the baud rate for MEMOBUS/Modbus
terminals R+, R-, S+ and S-. Cycle power for
the setting to take effect.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
0 to 8
3
A A A
426
H5-03
Communication Parity
Selection
Selects the communication parity for
MEMOBUS/Modbus terminals R+, R-, S+ and
S-. Cycle power for the setting to take effect.
0: No parity
1: Even parity
2: Odd parity
0 to 2
0
A A A
427