1.10 o: Operator Related Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
237
Pa
ra
m
et
er D
et
ai
ls
1
Setting 1: Enabled
The STOP key can be used to terminate the operation, even if the Run command source is
not assigned to the digital operator. If operation has been interrupted by pressing the STOP
key, the Run command must be cycled to restart the drive.
■
o2-03: User Parameter Default Value
Once drive parameters are set up completely, the values set can be saved as “User
Initialization Values” by setting parameter o2-03. Once this has been done, the “Initialize
Parameters” parameter (A1-03) will offer the choice of “1110: User Initialize”. Choosing
A1-03 = “1110: User Initialized”, will reset all parameters to the values saved as “User
Initialization Values”. Refer to
A1-03: Initialization on page 21
for details on drive
initialization.
Setting 0: No Change
All “User Initialization Values” are kept as they are.
Setting 1: Set User Initialization Values
The current parameter settings are saved as “User Initialization Values”. Once o2-03 is set to
1 and the ENTER key is pressed, the values are saved and the display returns to 0.
Setting 2: Clear User Initialization Values
All “User Initialization Values” are cleared. Once o2-03 is set to 2 and the ENTER key is
pressed, the values are erased and the display returns to 0. The setting “1111” will not longer
be available for initialization parameter A1-03.
■
o2-04: Drive Model Selection
Parameter o2-04 matches the control board to the drive hardware. Proper setting of o2-04 is
important for optimal performance and proper protection for the drive hardware. This
parameter is configured at the factory and does not normally require adjustment in the field.
It is available primarily to accommodate control board replacement in the event of damage.
Note:
1.
Refer to
Defaults Determined by Drive Capacity (o2-04) and Normal/Heavy Duty (C6-01) on
for a list of o2-04 settings and parameters that change depending on the drive model selection.
2.
Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions
will fail to operate properly.
No.
Name
Setting Range
Default
o2-03
User Parameter Default Value
0 to 2
0
No.
Name
Setting Range
Default
o2-04
Drive Model Selection
-
Depending on
drive size
Summary of Contents for OYMC V1000