2.9 MEMOBUS/Modbus Data Table
282
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
00C2H
Fault contents 5
bit 0
MEMOBUS/Modbus Communication Error (CE)
bit 1
Option Communication Error (bUS)
bit 4
Control Fault (CF)
bit 5
Reserved
bit 6
Option External Fault (EF0)
bit 7
PID Feedback Loss (FbL)
bit 8
Undertorque Detection 1 (UL3)
bit 9
Undertorque Detection 2 (UL4)
bit A
High Slip Braking Overload (oL7)
bit F
Hardware fault (includes oFx)
00C3H
Fault contents 6
bit 0 to 4
Reserved
bit 5
Output Current Imbalance (LF2)
bit 6
Pullout Detection (Sto)
bit 7
PG Disconnected (PGo)
bit 8
Reserved
bit A
Too many speed search restarts (SEr)
bit B to F
Reserved
00C4H
Fault contents 7
bit 0
PID Feedback Loss (FbH)
bit 1
External Fault 1, input terminal S1 (EF1)
bit 2
External Fault 2, input terminal S2 (EF2)
bit 3
Mechanical Weakening Detection 1 (oL5)
bit 4
Mechanical Weakening Detection 2 (UL5)
bit 5
Current Offset Fault (CoF)
bit 6
Reserved
bit 7
Reserved
bit 8
FBD’s Fault (dWFL)
Register No.
Contents