A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
331
Para
me
te
r Lis
t
A
61
External Search Command 1
Closed: Activates Current Detection Speed Search from
the max. output frequency (E1-04) if b3-01=0. Activates
Speed Estimation Type Speed search if b3-01 =1.
O O O
62
External Search Command 2
Closed: Activates Current Detection Speed Search from
the frequency reference b3-01=0. Activates Speed
Estimation Type Speed search if b3-01 =1.
O O O
65
KEB Ride-Thru 1 (N.C.)
Open: KEB Ride-Thru 1 enabled
Closed: Normal operation
O O O
66
KEB Ride-Thru 1 (N.O.)
Open: Normal operation
Closed: KEB Ride-Thru 1 enabled
O O O
67
Communications Test Mode
Tests the MEMOBUS/Modbus RS-485/422 interface.
O O O
68
High-Slip Braking
Closed: High-Slip braking is executed. Drive stops.
O
-
-
6A
Drive Enable
Open: Drive disabled.
If this input is opened during run, then the drive will stop
as specified by parameter b1-03.
Closed: Ready for operation.
O O O
75
Up 2 Command
Open: Maintains the current frequency reference
Closed: Increases or decreases the frequency reference.
UP 2 and Down 2 commands must be set in combination
with each other. The frequency reference source must be
assigned to the operator (b1-01 = “0”).
O O O
76
Down 2 Command
O O O
7A
KEB Ride-Thru 2 (N.C.)
Open: KEB Ride-Thru 2 enabled
Closed: Normal operation
O O O
7B
KEB Ride-Thru 2 (N.O.)
Open: Normal operation
Closed: KEB Ride-Thru 2 enabled
O O O
7C
Short-Circuit Braking (N.O.)
Open: Normal operation
Closed: Short-Circuit Braking
-
-
O
7D
Short-Circuit Braking (N.C.)
Open: Short-Circuit Braking
Closed: Normal operation
-
-
O
7E
Forward/Reverse Detection
Direction of rotation detection (for V/f with Simple PG
Feedback)
O
-
-
7F
Bi-directional PID output
selection
Enables or disables conversion of PID output to bi-
directional reference if parameter d4-11 = 1.
Open: Bi-directional output disabled
Closed: Bi-directional output enabled
O O O
90 to 96 FBD’s Digital Inputs 1 to 7
Reserved for FBD’s input functions
O O O
9F
FBD’s enable
Open: FBD’s enabled
Closed: FBD’s disabled
O O O
H1 Multi-Function Digital Input Selections
H1-
Setting
Function
Description
Control
Mode
Pg.
V/f
OL
V
PM