A.3 Control Mode Dependent Parameter Default Values
376
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Table A.2 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
Para-
meter
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Description
Setting
Range
Resolutio
n
Control Modes (E3-
01)
V/f (0)
OLV (2)
E3-04
Maximum output frequency
40.0 to 400.0
0.1 Hz
50.0
50.0
E3-05
Maximum output voltage
0.0 to 255.0
0.1 V
200.0
200.0
E3-06
Base Frequency
0.0 to 400.0
0.1Hz
50.0
50.0
E3-07
Middle output frequency
0.0 to 400.0
0.1Hz
2.5
3.0
E3-08
Middle output freq. voltage
0.0 to 255.0
0.1 V
16.0
14.4
E3-09
Minimum output frequency
0.0 to 400.0
0.1 Hz
1.3
0.5
E3-10
Minimum output voltage
0.0 to 255.0
0.1 V
12.0
3.0
E3-11
Middle output frequency 2
0.0 to 400.0
0.1 Hz
0.0
0.0
E3-12
Middle output freq. voltage 2
0.0 to 255.0
0.1 V
0.0
0.0
E3-13
0.0 to 255.0
0.1 V
0.0
0.0
E3-14
Motor 2 Slip compensation gain
0.0 to 2.5
0.1
0.0
1.0