1.1 A: Initialization
28
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 4: HVAC Fan Application
Table 1.11 HVAC Fan: Parameter Settings
Table 1.12 HVAC Fan: Preferred Parameters (A2-01 to A2-16)
Setting 5: Compressor Application
Table 1.13 Compressor: Parameter Settings
E1-03
V/f Pattern Selection
−
−
No.
Parameter Name
Optimum Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C6-01
Duty Rating
1: Normal Duty
C6-02
Carrier Frequency Selection
3: 8.0 kHz
H2-03
Terminals P2 Function Selection
39: Watt Hour Pulse Output
L2-01
Momentary Power Loss Operation
Selection
2: CPU Power Active - Drive will restart if
power returns prior to control power supply
shut down.
L8-03
Overheat Pre-Alarm Operation Selection
4: Operation at lower speed
L8-38
Carrier Frequency Reduction
2: Enabled across entire frequency range.
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection
E1-03
V/f Pattern Selection
b1-02
Run Command Selection
E1-04
Max Output Frequency
b1-04
Reverse Operation Selection
E2-01
Motor Rated Current
C1-01
Acceleration Time 1
H3-11
Terminal A2 Gain Setting
C1-02
Deceleration Time 1
H3-12
Terminal A2 Input Bias
C6-02
Carrier Frequency Selection
L2-01
Momentary Power Loss Operation
Selection
d2-01
Frequency Reference Upper Limit
L8-03
Overheat Pre-Alarm Operation
Selection
d2-02
Frequency Reference Lower Limit
o4-12
kWH Monitor Initial Value Selection
No.
Parameter Name
Optimum Setting
A1-02
Control Method Selection
0: V/f Control
No.
Parameter Name
No.
Parameter Name