1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
181
Pa
ra
m
et
er D
et
ai
ls
1
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting the
terminal AM output level can be set by a PLC via a communication option or MEMOBUS/
Modbus communications (through mode).
■
H4-02/H4-03: Multi-Function Analog Output Terminal AM Gain / Bias
Parameter H4-02 sets the output voltage that is equal to 100% of the monitor value.
Parameter H4-03 sets the output voltage equal to 0% of the monitor value.
Both values are set as a percentage of 10 V. The minimum output voltage for terminal AM is
0 V, the maximum is 10 Vdc.
illustrates how the gain and bias settings work.
Figure 1.72
Figure 1.72 Analog Output Gain/Bias Setting
When viewing the settings for H4-02, terminal AM will output a voltage that is equal to
100% of the monitor value (considering the present setting). When viewing the settings for
H4-03, terminal AM will output a voltage that is equal to 0% of the monitor value.
◆
H5: MEMOBUS/Modbus Serial Communication
Through the drives built in RS422/485 port (terminals R+, R-, S+, S-), serial communication
can be performed with programmable logic controllers (PLCs) or similar devices using the
MEMOBUS/Modbus protocol.
No.
Name
Setting Range
Default
H4-01
Multi-Function Analog 1 (Terminal AM Monitor
Selection)
000 to 999
102
No.
Name
Setting Range
Default
H4-02
Multi-Function Analog Output Terminal AM Gain
-999.9 to 999.9%
100.0%
H4-03
Multi-Function Analog Output Terminal AM Bias
-999.9 to 999.9%
0.0%
0 V
3 V
10 V
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor value
0%
Gain 50%
Bias 0%
Terminal AM
output
voltage
0 V
5 V
10 V
Gain 150%
Bias 0%
Gain 100%
Bias 0%
100%
Monitor value
0%
Terminal AM
output
voltage