2.9 MEMOBUS/Modbus Data Table
ME
MOBUS/Mo
dbus
C
ommuni
cat
io
ns
2
2.9
MEMOBUS/Modbus Data Table
Table below lists all MEMOBUS/Modbus data. There are three types of data: command
data, monitor data, and broadcast data.
◆
Command Data
It is possible to both read and write command data.
Note:
Bits that are not used should be set to 0. Refrain from writing to reserved registers.
Register No.
Contents
0000H
Reserved
0001H
Operation Signals and Multi-function Inputs
bit 0
H5-12 = 0: Forward Run Command (0 = Stop, 1 = Forward Run)
H5-12 = 1: Run Command (0 = Stop, 1 = Run)
bit 1
H5-12 = 0: Reverse Run Command (0 = Stop, 1 = Reverse Run)
H5-12 = 1: Forward/Reverse (0 = Forward, 1 = Reverse)
bit 2
External Fault (EF0)
bit 3
Fault Reset
bit 4
Multi-Function Input 1
Function is ComRef when H1-01 = 40 (Forward/Stop). Refer to
for
ComRef explanations.
bit 5
Multi-Function Input 2
Function is ComCtrl when H1-02 = 41 (Reverse/Stop). Refer to
ComCtrl explanations.
bit 6
Multi-Function Input 3
bit 7
Multi-Function Input 4
bit 8
Multi-Function Input 5
bit 9
Multi-Function Input 6
bit A
Reserved
bit B to bit F
Reserved
0002H
Frequency
Reference
Units are determined by parameter o1-03.
0003H
V/f Gain (V/f Control only)
0004H-0005H
Reserved
0006H
PID Target, 0.01% units, signed
0007H
Analog Output Terminal AM Setting (10 V / 4000 H)
0008H
Reserved