A.2 Parameter Table
358
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
o2-02
STOP Key Function
Selection
Enables/Disables the operator panel STOP key
when the drive is operated form external
sources (not operator).
0: Disabled
1: Enabled
0,1
1
A A A
506
o2-03
User Parameter
Default Value
Allows storing of parameter settings as a User
Initialization Selection (value 1110 for A1-03).
The value returns to 0 after entering 1 or 2.
0: No Change
1: Set Defaults - Saves current parameter
settings as user initialization.
2: Clear All - Clears the currently saved user
initialization.
0 to 2
0
A A A
507
o2-04
Drive Model Selection
Sets the drive model.
This parameter only needs to be set when
installing a new control board. Do not change
for other reason.
0 to FF
A A A
508
o2-05
Frequency Reference
Setting Method
Selection
Selects if the ENTER key must be pressed
when inputting the frequency reference by the
operator keypad.
0: Data/Enter key must be pressed to enter a
frequency reference.
1: Data/Enter key is not required. The
frequency reference is adjusted by the UP and
DOWN keys.
0, 1
0
A A A
509
o2-06
Operation Selection
when Digital Operator
is Disconnected
Sets drive action when the digital operator is
removed in LOCAL mode or with b1-02 = 0.
0: The drive will continue operation
1: The drive will trigger a fault (OPR) and the
motor will coast to stop
0, 1
0
A A A
50A
o2-07
Motor Direction at
Power Up when Using
Operator
0: Forward
1: Reverse
This parameter requires that drive operation be
assigned to the digital operator.
0 to 1
0
A A A
527
o2-09
Initialization mode
Changes some parameter default settings
depending on the region.
0 to 3
dep.
on
drive
spec.
A A A
50D
o4: Maintenance Period
Use o4 parameters to perform maintenance.
o4-01
Accumulated
Operation Time
Setting
Sets the value for the cumulative operation time
of the drive in units of 10 h.
0 to
9999
0
A A A
50B
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...