1.10 o: Operator Related Settings
238
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
■
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be used to input a frequency reference from the digital
operator.
Setting 0: ENTER Key Required
Every change in the frequency reference setting on the digital operator has to be finalized by
pressing the ENTER key before it becomes effective.
Setting 1: ENTER Key Not Required
The output frequency changes immediately when the reference is changed by the UP and
DOWN key on the digital operator. The ENTER key does not need to be pressed. The
frequency reference is saved five seconds after the Up or DOWN key has been released.
■
o2-06: Operation Selection when Digital LCD Operator is Disconnected
Determines if the drive will stop when an external LCD operator is removed in LOCAL
mode or with b1-02/16 set to 0.
Note:
An LCD operator is available as an option. This setting is not applicable to the
standard LED operator that comes with the drive.
Setting 0: Continue Operation
The operation is continued.
Setting 1: Trigger a Fault
The operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.
■
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up when the Run
command is set to be given from the digital operator.
Note:
This parameter is effective only when the Run command is set to be given from the
digital operator (b1-02/16 = 0).
No.
Name
Setting Range
Default
o2-05
Frequency Reference Setting Method Selection
0 or 1
0
No.
Name
Setting Range
Default
o2-06
LCD Operator Disconnection Operation
0 or 1
0
No.
Name
Setting Range
Default
o2-07
Motor Direction at Power Up when Using
Operator
0 or 1
0