Two inputs (FWD/Stop-REV/Stop). Initializing the drive by setting A1-01 = 2220, presets
the terminals S1 and S2 to these functions. This is the default setting of the drive. Also
refer to
Setting 40/41: Forward Run / Reverse Run Command for 2-Wire Sequence on
• 2-wire sequence 2:
Two inputs (Start/Stop-FWD/REV). Also refer to
Setting 42/43: Run and Direction
Command for 2-Wire Sequence 2 on page 152
.
• 3-wire sequence:
Inputs S1,S2,S3 (Start-Stop-FWD/REV). Initialize the drive by setting A1-01 = 3330
presets the terminals S1, S2 and S3 to these functions. Also refer to
Setting 2: MEMOBUS/Modbus Communications
To issue a Run command via serial communications, set b1-02 to “2” and connect the RS-
485/422 serial communication cable to R+, R-, S+, and S- on the removable terminal block.
For information, refer to
Refer to MEMOBUS/Modbus Communications on page 257
Setting 3: Option Card
To issue the Run command via the communication option board, set b1-02 to “3” and plug a
communication option board into the 2CN port on the control PCB. Refer to the manual
supplied with the option board for instructions on integrating the drive into the
communication system.
Note:
If b1-01 is set to 3, but an option board is not installed in 2CN, an OPE05 operator programming
error will be displayed on the digital operator and the drive will not run.
■
b1-03: Stopping Method Selection
Select how the drive stops the motor when a Stop command is entered or when the Run
command is removed.
Setting 0: Ramp to Stop
When the Run command is removed, the drive will decelerate the motor to stop. The
deceleration rate is determined by the active deceleration time. The default deceleration time
is set to parameter C1-02.
DC Injection braking (for IM control) or Short Circuit Braking (PM Open Loop Vector) can
be applied at the end of the ramp in order to completely stop high inertia loads. Refer to
Refer to b2: DC Injection Braking on page 47
for details.
No.
Parameter Name
Setting Range
Default
b1-03
Stopping Method Selection
0 to 3, 9
1
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...