1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
157
Pa
ra
m
et
er D
et
ai
ls
1
If the digital input is open, the PID output builds the output frequency reference. If the input
is closed, the PID output is converted to bi-directional output frequency reference. Also refer
to
d4-11: Bi-Directional Output Selection on page HIDDEN
Setting 90 to 96: FBD’s Digital Input 1 to 7
These settings are for digital inputs functions used by FBD’s. Normally there is no need to
change or apply these settings.
Setting 9F: FBD’s Function Disable
This function is used to enable or disable a FBD’s program in the drive. An input
programmed for this function is effective only if A1-07 = 2.
◆
H2: Multi-Function Outputs
■
H2-01 to H2-03: Terminal MA/MB/MC, P1/PC and P2/PC Function Selection
The drive has three multi-function output terminals. Set parameters H2-01 to H2-03 between
0 and 192 to assign functions to these terminals. Default values are listed in the table below.
Note:
If not using an input terminal or if using it in the through-mode, be sure to set that terminal to
“F”.
Table 1.42 Multi-Function Output Terminal Settings
Status
Description
Open
FBD’s enabled
Closed
FBD’s disabled
No.
Parameter Name
Setting
Range
Default
H2-01
Terminal MA, MB and MC Function Selection (relay)
0 to 192
E: Fault
H2-02
Terminal P1 Function Selection (open-collector)
0 to 192
0: During Run
H2-03
Terminal P2 Function Selection (open-collector)
0 to 192
2: Speed Agree 1
Setting
Function
Page
Setting
Function
Page
0
During Run
19
Torque Detection 2 (N.C.)
1
Zero Speed
1A
During Reverse Operation
2
Speed Agree 1
1B
During Baseblock (N.C.)
3
User Set Speed Agree 1
1C
Motor 2 Selection
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...