L4-07: Speed Agreement Detection Selection
Determines when frequency detection is active using parameters L4-01 through L4-04.
Setting 0: No Detection during Baseblock
Setting 1: Detection Always Enabled
◆
L5: Fault Restart
The drive can be set up to performs a self-diagnostic check and resume the operation after a
fault has occurred. If the self-check is successful and the cause of the fault has disappeared,
the drive restarts by performing Speed Search (refer to
details).
The drive can attempt to restart itself following the faults listed below.
Use parameters L5-01 to L5-05 to set up automatic fault restart.
To output a signal during fault restart, set H2-01, H2-02, or H2-03 to 1E.
Do not use the fault restart function in hoist applications.
■
L5-01: Number of Auto Restart Attempts
Sets the number of number of times that the drive may attempt to restart itself.
No.
Name
Setting Range
Default
L4-07
Speed Agreement Detection Selection
0 or 1
0
• GF (Ground
Fault)
• oL4 (Overtorque
2)
• LF
(Output Open Phase)
• ov
(DC Bus Overvoltage)
• oC
(Overcurrent)
• PF
(Input Phase Loss)
• oH1 (Drive
Overheat)
• rH (Braking
Resistor
Fault)
• oL1
(Motor Overload)
• rr
(Braking Transistor Fault)
• oL2 (Drive
Overload)
• Uv1
<1> When L2-01 is set to 1 or 2 (continue operation during momentary power loss)
(DC Bus Undervoltage)
• oL3 (Overtorque
1)