A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
333
Para
me
te
r Lis
t
A
6
Drive Ready
Closed: Drive Ready. The drive is powered up, not in a fault state,
and in the Drive mode.
O O O
7
DC Bus Undervoltage
Closed: DC bus voltage is below the UV trip level set in L2-05.
O O O
8
During Baseblock
(N.O.)
Closed: There is no output voltage
O O O
9
Frequency reference
selection
Open: External Reference 1 or 2 supplies the frequency reference
Closed: Digital operator supplies the frequency reference.
O O O
A
Run command selection
Open: External Reference 1 or 2 supplies the Run command
Closed: Digital operator supplies the Run command.
O O O
B
Torque Detection 1
(N.O.)
Closed: Output current/torque exceeds the torque value set in
parameter L6-02 for longer than the time set in parameter L6-03.
O O O
C
Frequency Reference
Loss
Closed: Loss of the analog frequency reference detected. Enabled
when L4-05 = 1.
O O O
D
Braking Resistor Fault
Closed: Braking resistor or transistor is overheated or faulted out.
This selection requires that braking resistor protection parameter be
set for ERF (L8-01 = “1”).
O O O
E
Fault
Closed: Fault occurred (other than CPF00 and CPF01).
O O O
F
Not used
Set this value when the terminal is not used, or when using the
terminal in the pass-through mode.
O O O
10
Minor Fault
Closed: An alarm is triggered.
O O O
11
Reset Command Active Closed: Reset command to the drive is active.
O O O
12
Timer Output
Timer output, controlled by b4-01 and b4-02. Used in conjunction
with the digital input (H1-
= 18 “timer function”).
O O O
13
Speed Agree 2
Closed: When drive output frequency equals the frequency
ref/- L4-04.
O O O
14
User Set Speed Agree 2
Closed: When the drive output frequency is equal to the value in
L4-03 (plus or minus L4-04).
O O O
15
Frequency Detection 3
Closed: When the drive output frequency is less than or equal to the
value in L4-03 with the hysteresis determined by L4-04.
O O O
16
Frequency Detection 4
Closed: When the output frequency is greater than or equal to the
value in L4-03 with the hysteresis determined by L4-04.
O O O
17
Torque Detection 1
(N.C.)
Open: When the output current/torque exceeds the value set in
parameter L6-02 for more time than is set in parameter L6-03.
O O O
18
Torque Detection 2
(N.O.)
Closed: When the output current/torque exceeds the value set in
parameter L6-05 for more time than is set in parameter L6-06.
O O O
19
Torque Detection 2
(N.C.)
Open: Output current/torque exceeds the value set in parameter L6-
05 for more time than is set in parameter L6-06.
O O O
H2 Multi-Function Digital Output Settings
H2-
Setting
Function
Description
Control
Mode
Pg.
V/f
O
LV
P
M