1.1 A: Initialization
30
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Table 1.16 Hoist: Preferred Parameters (A2-01 to A2-16):
Notes on Controlling the Brake when Using the Hoist Application Preset
1. The frequency detection function is used for controlling the brake.
d1-02
Frequency Reference 2
30.0 Hz
d1-03
Frequency Reference 3
50.0 Hz
E1-03
V/f Pattern Selection
0FH
H2-02
Terminals P1 Function Selection
37: During Frequency Output
H2-03
Terminals P2 Function Selection
5: Frequency Detection 2
L2-03
Momentary Power Loss Minimum
Baseblock Time
0.3 s
L3-04
Momentary Power Loss Voltage Recovery
Ramp Time
0: Disabled
L4-01
Speed Agreement Detection Level
2.0 Hz
L4-02
Speed Agreement Detection Width
0.0 Hz
L6-01
Torque Detection Selection 1
8: UL3 at RUN - Fault
L6-02
Torque Detection Level 1
5%
L6-03
Torque Detection Time 1
0.5 s
L8-05
Input Phase Loss Protection Selection
1: Enabled
L8-07
Output Phase Loss Protection
1: Enabled
L8-38
Carrier Frequency Reduction
1: Enabled below 6 Hz
L8-41
Current Alarm Selection
1: Enabled (alarm is output)
No.
Parameter Name
No.
Parameter Name
A1-02
Control Method Selection
d1-02
Frequency Reference 2
b1-01
Frequency Reference Selection
d1-03
Frequency Reference 3
b6-01
Dwell Reference at Start
E1-08
Mid Output Frequency Voltage
b6-02
Dwell Time at Start
H2-01
Terminals MA, MB, and MC Function
Selection
C1-01
Acceleration Time 1
L1-01
Motor Overload Protection Selection
C1-02
Deceleration Time 1
L4-01
Speed Agreement Detection Level
C6-02
Carrier Frequency Selection
L6-02
Torque Detection Level 1
d1-01
Frequency Reference 1
L6-03
Torque Detection Time 1
No.
Parameter Name
Optimum Setting
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...