1.10 o: Operator Related Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
239
Pa
ra
m
et
er D
et
ai
ls
1
Setting 0: Forward
Setting 1: Reverse
■
o2-09: Initialization Specification Selection
This parameter sets the regional specifications for the drive and should not be changed.
◆
o4: Maintenance Monitor Settings
■
o4-01: Accumulated Operation Time Setting
Parameter o4-01 sets the cumulative operation time and allows the user to set the starting
value of the accumulated operation time displayed in monitor U4-01.
Note:
The value in o4-01 is set in 10 h units. For example, a setting of 30 will set the cumulative
operation time counter to 300 h. 300 h will also be displayed in monitor U4-01.
■
o4-02: Accumulated Operation Time Selection
Selects the conditions for what is to be considered "accumulated operation time."
Accumulated operation time is displayed in U4-01.
Setting 0: Power On Time
The drive logs the time it is connected to a power supply, no matter if the motor is running or
not.
Setting 1: Run Time
The drive logs the time that the output is active, i.e., whenever a Run command is active
(even if the motor is not rotating) or a voltage is output.
■
o4-03: Cooling Fan Operation Time / Maintenance Setting
Sets the value of the cooling fan operation time counter displayed in monitor U4-03.
Parameter o4-03 also sets the base value used for the cooling fan maintenance value
displayed in U4-04. Be sure to reset this parameter back to 0 if the cooling fan is replaced.
Note:
1.
The value in o4-03 is set in 10 h units. For example, a setting of 30 will set the cooling fan operation
time counter to 300 h. “300” will be displayed in monitor U4-03.
2.
The actual maintenance time depends on the environment the drive is used in.
No.
Name
Setting Range
Default
o4-01
Accumulated Operation Time Setting
0 to 9999
0
No.
Name
Setting Range
Default
o4-02
Accumulated Operation Time Selection
0 or 1
0