1.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
111
Pa
ra
m
et
er D
et
ai
ls
1
The tables below show details on pre-defined V/f patterns.
•
V/f Patterns for 0.1 to 4.0 kW Drives
The following graphs are for 200 V class drives. Double values when using a 400 V class
unit.
Table 1.31 Constant Torque Characteristics, Settings 0 to 3
Table 1.32 Derated Torque Characteristics, Settings 4 to 7
4
50 Hz, Heavy Duty 2
Derated torque
For fans, pumps, and other applications
that require torque derating relative to the
load.
5
50 Hz, Heavy Duty 1
6
50 Hz, Heavy Duty 1
7
50 Hz, Heavy Duty 2
8
50 Hz, mid starting torque
High starting torque
Select high starting torque when:
• Wiring between the drive an motor
exceeds 150 m
• A large amount of starting torque is
required
• An AC reactor is installed
9
50 Hz, high starting torque
A
60 Hz, mid starting torque
B
60 Hz, high starting torque
C
90 Hz (with 60 Hz base)
Constant output
When operating at greater than 60 Hz the
output voltage will be constant.
D
120 Hz (with 60 Hz base)
E
180 Hz (with 60 Hz base)
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
Setting
Specification
Characteristic
Application
V
oltage (V)
Frequency (Hz)
0
12
200
1.3 2.5
50
16
V
oltage (V)
Frequency (Hz)
0
12
16
200
1.5 3
60
V
oltage (V)
Frequency (Hz)
0
12
16
200
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
12
16
200
1.5 3
72
60