A.6 Parameters that Change with the Motor Code Selection
390
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Table A.11 400 V, 1750 rpm Type Yaskawa SSR1 Series Motor
Par.
Description
Unit
Default Settings
E5-01
Motor Code
−
1232
1233
1235
1236
1238
Voltage class
−
400 Vac
400 Vac
400 Vac
400 Vac
400 Vac
Rated power
−
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.7 kW
Rated speed
r/min
1750
1750
1750
1750
1750
E5-02
Motor rated power
kW
0.4
0.75
1.5
2.2
3.7
E5-03
Motor rated current
A
0.83
1.49
2.75
4.05
6.80
E5-04
Motor pole number
–
6
6
6
6
6
E5-05
Motor winding resistance
W
32.932
9.136
6.004
3.297
1.798
E5-06
d-axis inductance
mH
219.36
92.08
68.32
40.39
32.93
E5-07
q-axis inductance
mH
256.40
119.56
85.56
48.82
37.70
E5-09
Induction voltage constant 1
mVs/rad
466.0
459.0
501.8
485.7
498.7
E5-24
Induction voltage constant 2 mV/(r/min)
0.0
0.0
0.0
0.0
0.0
E1-04
Maximum output frequency
Hz
87.5
87.5
87.5
87.5
87.5
E1-05
Maximum output voltage
V
380.0
380.0
380.0
380.0
380.0
E1-06
Base voltage
Hz
87.5
87.5
87.5
87.5
87.5
E1-09
Minimum output frequency
Hz
4.4
4.4
4.4
4.4
4.4
L3-24
Motor acceleration time
s
0.092
0.076
0.051
0.066
0.075
n8-49
Pull-in current
%
–7.2
–10.7
–11.1
–8.9
–7.9