A.2 Parameter Table
324
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
F1-08
Overspeed Detection
Level
Sets the speed feedback level which has to be
exceeded for the time set in F1-09 before an OS
fault will occur.
Set as a percentage of the maximum output
frequency (E1-04).
0 to 120 115% A
− −
387
F1-09
Overspeed Detection
Delay Time
Sets the time in seconds for which the speed
feedback has to exceed the overspeed detection
level F1-08 before an OS fault will occur.
0.0 to
2.0
1.0
A
− −
388
F1-10
Excessive Speed
Deviation Detection
Level
Sets the allowable deviation between motor
speed and frequency reference before a speed
deviation fault (DEV) is triggered.
Set as a percentage of the maximum output
frequency (E1-04).
0 to 50 10% A
− −
389
F1-11
Excessive Speed
Deviation Detection
Delay Time
Sets the time in seconds for which a deviation
between motor speed and frequency reference
has to exceed the speed deviation detection
level F1-10 before a DEV fault will occur.
0.0 to
10.0
0.5 s A
− −
38A
F1-14
PG Open-Circuit
Detection Time
Sets the time for which no PG pulses must be
detected before a PG Open (PGO) fault is
triggered.
0.0 to
10.0
2.0 s A
− −
38D
F6 and F7: Serial Communications Option Card Settings
Use F6 parameters to program the drive for serial communication.
F6-01
Communications Error
operation Selection
Selects the operation after a communications
error occurred.
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast Stop using C1-09
3: Alarm only
0 to 3
1
A A A
3A2
F6-02
External fault from
comm. option
selection
Sets when an external fault from a comm option
is detected.
0: Always detected
1: Detection during Run only
0 or 1
0
A A A
3A3
F6-03
External fault from
comm. option
operation selection
Selects the operation after an external fault set
by a communications option (EF0).
0: Ramp to stop using current accel/decel time
1: Coast to stop
2: Fast Stop using C1-09
3: Alarm only
0 to 3
1
A A A
3A4
F6-04
Bus Error Detection
Time
Set the delay time for error detection if a bus
error occurs.
0.0 to
5.0
2.0 s A A A
3A5
F6-10
CC-Link Node
Address
Sets the node address if a CC-Link option card
is installed.
0 to 63
0
A A A
3E6
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...