1.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
129
Pa
ra
m
et
er D
et
ai
ls
1
■
F1-04: Operation Selection at Deviation
Sets the stopping method when a speed deviation (dEv) fault occurs. Refer to
setting explanations.
■
F1-08/F1-09: Overspeed Detection Level / Delay Time
F1-08 sets the detection level for an overspeed (oS) fault as a percentage of the maximum
output frequency. The speed feedback has to exceed this level for longer than the time set in
F1-09 before a fault is detected.
■
F1-10/F1-11: Excessive Speed Deviation Detection Level / Delay Time
F1-10 sets the detection level for a speed deviation (dEv) fault as a percentage of the
maximum output frequency. The speed feedback has to exceed this level for longer than the
time set in F1-11 before a fault is detected. Speed deviation is the difference between actual
motor speed and the frequency reference command.
■
F1-14: PG Open-Circuit Detection Time
Sets the time required to detect PGo if no pulse signal is present at terminal RP.
No.
Parameter Name
Setting Range
Default
F1-03
Operation Selection at Overspeed (oS)
0 to 3
1
No.
Parameter Name
Setting Range
Default
F1-04
Operation Selection at Deviation (dEv)
0 to 3
3
No.
Parameter Name
Setting Range
Default
F1-08
Overspeed Detection Level
0 to 120%
115%
F1-09
Overspeed Detection Delay Time
0.0 to 2.0 s
1.0 s
No.
Parameter Name
Setting Range
Default
F1-10
Excessive Speed Deviation Detection Level
0 to 50%
10%
F1-11
Excessive Speed Deviation Detection Delay Time
0.0 to 10.0 s
0.5 s
No.
Parameter Name
Setting Range
Default
F1-14
PG Open-Circuit Detection Time
0.0 to 10.0 s
2.0 s