A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
329
Para
me
te
r Lis
t
A
7
Accel/Decel Time 1
Used to switch between Accel/Decel. Time 1/2
O O O
8
Baseblock Command (N.O.)
Open: Normal operation
Closed: No drive output
O O O
9
Baseblock Command (N.C.)
Open: No drive output
Closed: Normal operation
O O O
A
Accel/Decel Ramp Hold
Closed: The drive pauses during acceleration or
deceleration and maintains the output frequency.
O O O
B
Drive Overheat Alarm (OH2)
Closed: Displays an OH2 alarm
O O O
C
Terminal A2 Enable
Open: Terminal A2 disabled
Closed: Terminal A2 enabled
O O O
F
Not used
Select this setting when not using the terminal or when
using the terminal in a pass-through mode.
O O O
10
Up Command
Open: Maintains the current frequency reference
Closed: Increases or decreases the current frequency
reference.
Ensure that the increase and decrease commands are set in
conjunction with one another. The frequency reference
source must be set to operator (b1-01 = 0).
O O O
11
Down Command
O O O
12
Forward Jog
Closed: Runs forward at the Jog Frequency d1-17.
O O O
13
Reverse Jog
Closed: Runs reverse at the Jog Frequency d1-17.
O O O
14
Fault Reset
Closed: Resets faults if the cause is cleared and the Run
command is removed.
O O O
15
Fast-Stop (N.O.)
Closed: Decelerates at the Fast-Stop time C1-09.
To restart the Fast-Stop input must be released and Run
must be cycled.
O O O
16
Motor 2 Selection
Open: Motor 1 (E1-
, E2-
)
Closed: Motor 2 (E3-
, E4-
)
O O O
17
Fast-stop (N.C.)
Open: Decelerates according to C1-09 (Fast-stop Time)
O O O
18
Timer Function
Input
Set the timer delay using parameters b4-01 and b4-02.
Ensure this function is set in conjunction with the multi-
function output timer (H2-
= 12).
O O O
19
PID Disable
Closed: PID control disabled
O O O
1A
Accel/Decel Time Selection 2
Switches Accel/Decel times.
O O O
1B
Program Lockout
Open: Parameters can not be edited. (except U1-01 if
reference source is set for operator)
Closed: Parameters may be edited and saved.
O O O
1E
Reference Sample Hold
Closed: Samples the analog frequency reference and
operates the drive at that speed.
O O O
H1 Multi-Function Digital Input Selections
H1-
Setting
Function
Description
Control
Mode
Pg.
V/f
OL
V
PM