1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
163
Pa
ra
m
et
er D
et
ai
ls
1
Setting 7: DC Bus Undervoltage
Output closes whenever the DC bus voltage or control circuit power supply drops below the
trip level. The undervoltage trip level is determined by L2-05. A fault in the DC bus charge
circuit will also cause the DC Bus Undervoltage output to close.
Setting 8: During Baseblock (N.O.)
Output closes to indicate that the drive is in a baseblock state. While Baseblock is executed,
output transistors are not switched and no voltage will be output.
Setting 9: Frequency Reference Source
A digital output programmed for this function shows the frequency reference source that is
currently selected.
Setting A: Run Command Source
A digital output programmed for this function shows the Run command source that is
currently selected.
Status
Description
Open
DC bus voltage is above the level set to L2-05
Closed
DC bus voltage has fallen below the trip level set to L2-05.
Status
Description
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Status
Description
Open
Frequency reference is provided from External Reference 1 (b1-01) or 2 (b1-15)
Closed
Frequency reference is being sourced from the digital operator.
Status
Description
Open
Run command is provided from External Reference 1 (b1-02) or 2 (b1-16)
Closed
Run command is being sourced from the digital operator.