1.4 d: Reference Settings
104
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Figure 1.38
Figure 1.38 Up/Down 2 Bias when d4-03 = 0.0 Hz
Setting d4-03 > 0.0 Hz
When an Up 2 or Down 2 command is enabled, the bias is increased or decreased in steps for
the value set in d4-03. The frequency reference changes with the accel/decel times
determined by parameter d4-04.
Figure 1.39
Figure 1.39 Up/Down 2 Bias when d4-03 > 0.0 Hz
■
d4-04: Frequency Reference Bias Accel/Decel (Up/Down 2)
Parameter d4-04 determines the accel/decel times that are used for increasing/decreasing the
frequency reference or bias when the Up/Down 2 function is used.
No.
Parameter Name
Setting Range
Default
d4-04
Frequency Reference Bias Accel/Decel
0 or 1
0
Bias
Output
frequency
Bias value is increased using the
accel/decel times as set in d4-04
Up 2 command
Bias
Output
frequency
Bias value is increased in steps as
defined in d4-03
Drive uses accel/decel times as
set in d4-04
Up 2 command