1.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
183
Pa
ra
m
et
er D
et
ai
ls
1
■
H6-02: Pulse Train Input Terminal RP Scaling
The pulse train input scaling parameter sets the terminal RP input frequency that is equal to
100% of the signal selected as the input value in parameter H6-01.
■
H6-03: Pulse Train Input Terminal RP Gain
Sets the level of the value selected in H6-01 when a pulse train signal with the frequency set
in H6-02 is input to terminal RP.
■
H6-04: Pulse Train Input Terminal RP Bias
Sets the level of the value selected in H6-01 when a 0 Hz signal is input to terminal RP.
■
H6-05: Pulse Train Input Terminal RP Filter Time
Sets the pulse train input filter time constant in seconds.
■
H6-06: Pulse Train Output Terminal MP Monitor Selection
Selects the pulse train monitor output terminal MP function. The set value
is equal to
the numerals in U -
of the selected monitor. Refer to
complete list of monitors. Selectable monitor items are listed below.
No.
Name
Setting Range
Default
H6-02
Pulse Train Input Scaling
1000 to 32000 Hz
1440 Hz
No.
Name
Setting Range
Default
H6-03
Pulse Train Input Gain
0.0 to 1000.0%
100.0%
No.
Name
Setting Range
Default
H6-04
Pulse Train Input Bias
-100.0 to 100.0%
0.0%
No.
Name
Setting Range
Default
H6-05
Pulse Train Input Filter Time
0.00 to 2.00 s
0.10 s
No.
Name
Setting Range
Default
H6-06
Pulse Train Output Terminal MP Monitor
Selection
000, 031, 101, 102,
105, 116, 501, 502,
801 to 809
102