1.6 F: Option Settings
134
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
■
F6-51: DeviceNet Communication Speed
Sets the communication speed for a DeviceNet option card if installed.
Settings:
■
F6-52: DeviceNet PCA Setting
Defines the data format for data the drive receives from the DeviceNet master.
■
F6-53: DeviceNet PPA Setting
Defines the data format for data sent from the drive to the DeviceNet master.
■
F6-54: DeviceNet Idle Mode Fault Detection
Determines if the drive detects an EF0 fault, e.g. when no data are receive from the master
(e.g., when the master is in idle mode).
No.
Parameter Name
Setting Range
Default
F6-50
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-20 in older software.
DeviceNet MAC Address
0 to 63
0
No.
Parameter Name
Setting Range
Default
F6-51
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-21 in older software
DeviceNet Communication Speed
0 to 4
3
F6-51
Communication Speed
F6-51
Communication Speed
0
125 kbps
3
Adjustable from Network
1
250 kbps
4
Auto detection
2
500 kbps
No.
Parameter Name
Setting Range
Default
F6-52
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-22 in older software.
DeviceNet PCA Setting
0 to 255
0
No.
Parameter Name
Setting Range
Default
F6-53
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-23 in older software.
DeviceNet PPA Setting
0 to 255
0
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...