E4-09: Motor 2 Mechanical Loss
Sets the motor mechanical loss as a percentage of motor rated power (kW).
This parameter seldom needs to be changed, but may need to be adjusted in the following
circumstances:
• When there is a large amount of torque loss due to motor bearing friction.
• When there is a large amount of torque loss in a fan or pump application.
■
E4-10: Motor 2 Iron Loss
Sets the motor 2 iron loss in watts.
■
E4-11: Motor 2 Rated Power
Sets the motor 2 rated power. During Auto-Tuning the value must entered to parameter T1-
02. If Auto-Tuning completes successfully, the entered value will automatically be saved to
E4-11.
■
E4-12: Motor 2 Iron-Core Saturation Coefficient 3
Sets the motor 2 iron saturation coefficient at 130% of magnetic flux.
No.
Parameter Name
Setting Range
Default
E4-08
Motor 2 Motor Iron-Core Saturation Coefficient 2
[E4-07] to 0.75
0.75
No.
Parameter Name
Setting Range
Default
E4-09
Motor 2 Mechanical Loss
0.00 to 10.0%
0.0%
No.
Parameter Name
Setting Range
Default
E4-10
Motor 2 Iron Loss
0 to 65535 W
Depending on
o2-04
No.
Parameter Name
Setting Range
Default
E4-11
Motor 2 Rated Power
0.00 to 650.00 kW
Depending on
o2-04
No.
Parameter Name
Setting Range
Default
E4-12
Motor 2 Iron-Core Saturation Coefficient 3
1.30 to 5.00
1.30