A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
335
Para
me
te
r Lis
t
A
4D
OH Pre-alarm Time
Limit
Closed: OH Pre-alarm time limit is passed.
O O O
90 to 92
FBD’s Digital Outputs
1 to 3
Reserved for FBD’s digital output functions.
O O O
100 to
14D
H2 Parameter Functions
Reversed Output
Switching of 0 to 92
Reverse the output switching of the multi-function output
functions. Set the last two digits of 1
to reverse the output
signal of that specific function.
Examples:
Setting “108” reverses the output of “During baseblock,” which is
setting value 08.
Setting “14A” reverses the output of “During KEB operation”,
which is setting “4A”.
O O O
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
H3: Analog Inputs
Use H3 parameters to set the multi-function analog input terminals.
H3-01
Terminal A1 Signal
Level Selection
Sets the input level for terminal A1.
0: 0 to +10 V (lower limit)
1: 0 to +10 V (no lower limit)
0, 1
0
A A A
410
H3-02
Terminal A1 Function
Selection
Sets the function of terminal A1.
When terminal A1 is not used or is used as a
through terminal, this parameter must be set to
“F”.
0 to 31
0
A A A
434
H3-03
Terminal A1 Gain
Setting
Sets the level of the input value selected in H3-
02 when 10V is input at terminal A1.
-999.9 to
999.9
100.0
%
A A A
411
H3-04
Terminal A1 Bias
Setting
Sets the level of the input value selected in H3-
02 when 0V is input at terminal A1.
-999.9 to
999.9
0.0% A A A
412
H3-09
Terminal A2 Signal
Level Selection
Sets the input signal level for terminal A2.
0: 0 to +10 V (with lower limit)
1: 0 to +10 V (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
2
A A A
417
Switch between current or voltage
inputs by using DIP switch S1-2
switch on the terminal board.
H3-10
Terminal A2 Function
Selection
Sets the function of terminal A2.
When terminal A2 is not used or is used as a
through terminal, this parameter must be set to
“F”.
0 to 31
0
A A A
418
H2 Multi-Function Digital Output Settings
H2-
Setting
Function
Description
Control
Mode
Pg.
V/f
O
LV
P
M