1.5 E: Motor Parameters
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
127
Pa
ra
m
et
er D
et
ai
ls
1
2.
This parameter is not reset when the drive is initialized using A1-03.
■
E5-24: Motor Induction Voltage Parameter 2 (PM OLV)
Set the induced phase-to-phase rms voltage in units of 0.1 mV/(r/min) [mechanical angle].
Set this parameter when using an SMRA series pico motor.
When E5-01 is set to “FFFF” use either E5-09 or E5-24 for setting the voltage constant.
Note:
1.
Ensure that E5-09 = 0 when setting parameter E5-24. An alarm will be triggered, however, if both E5-
09 and E5-24 are set 0, or if neither parameter is set to 0.
2.
This parameter is not reset when the drive is initialized using A1-03.
No.
Parameter Name
Setting Range
Default
E5-24
Motor Induction Voltage Parameter 2 (PM OLV)
0.0 to 2000.0
mV/(r/min)
Depending on
E5-01