YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
255
1.12 U: Monitor Parameters
Pa
ra
m
et
er D
et
ai
ls
1
1.12 U: Monitor Parameters
Monitor parameters let the user view various aspects of drive performance as it is shown on
the operator display.
Some monitors can be output from terminal AM by assigning the specific monitor parameter
number to H4-01. Refer to
H4-01: Multi-Function Analog Terminal AM Monitor
for details on assigning functions to the analog output.
◆
U1: Operation Status Monitors
Status monitors display drive status like output frequency, current etc. Refer to page
for
a complete list of U1-
monitors and descriptions.
◆
U2: Fault Trace
These monitor parameters are used to view the status of various drive aspects when a fault
occurs. This information is helpful for finding out why a fault occurred. Refer to page
for a complete list of U2-
monitors and descriptions.
U2-
monitors are not reset when the drive is initialized. Refer to
for instructions to initialize the fault trace.
◆
U3: Fault History
These parameters display faults that have occurred during operation as well as the drive
operation time when those faults occurred. Refer to page
for a complete list of U3-
monitors and descriptions.
U3-
monitors are not reset when the drive is initialized. Refer to
for instructions to initialize the fault trace.
◆
U4: Maintenance Monitors
Maintenance monitors show:
• Runtime data of the drive and cooling fans, and number of Run commands issued.
• Maintenance data and replacement information for various drive components.
• kWh data.
• Highest peak current that has occurred and output frequency at the time the peak current
occurred.
• Motor overload status information.
• Detailed information about the present Run command and frequency reference source
selection.