1.10 o: Operator Related Settings
240
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
■
o4-05: Capacitor Maintenance Setting
Sets value of the maintenance monitor for the DC bus capacitors displayed in U4-05 as a
percentage of the total expected performance life. This value should be reset to 0 when the
DC bus capacitors have been replaced.
Note:
The actual maintenance time will depend on the environment the drive is used in.
■
o4-07: Softcharge Bypass Relay Maintenance Setting
Sets the value of the softcharge bypass relay maintenance time displayed in U4-06 as a
percentage of the total expected performance life. This value should be reset to 0 when the
relay has been replaced.
Note:
The maintenance actual time depends on the environment the drive is used in.
■
o4-09: IGBT Maintenance Setting
Sets the value of the IGBT maintenance time displayed in U4-07 as a percentage of the total
expected performance life. This value should be reset to 0 when the IGBTs have been
replaced.
Note:
The actual maintenance time depends on the environment the drive is used in.
■
o4-11: U2, U3 Initialization
When the drive initialized, the fault trace and fault history monitors (U2-
and
U3-
) are not reset. Parameter o4-11 can be used to initialize them.
No.
Name
Setting Range
Default
o4-03
Cooling Fan Operation Time
0 to 9999
0
No.
Name
Setting Range
Default
o4-05
Capacitor Maintenance Setting
0 to 150%
0%
No.
Name
Setting Range
Default
o4-07
Inrush Prevention Relay Maintenance Setting
0 to 150%
0%
No.
Name
Setting Range
Default
o4-09
IGBT Maintenance Setting
0 to 150%
0%
No.
Name
Setting Range
Default
o4-11
U2, U3 Initialization
0 or 1
0