A.5 Defaults Determined by Drive Capacity (o2-04) and Normal/Heavy
380
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Table A.6 Three-Phase, 200 V Class Drives
Default Settings by Drive Capacity and ND/HD Setting
No.
Description
Unit
Default Settings
−
Model VZA
−
20P1
20P2
20P4
20P7
21P5
C6-01
Normal/Heavy Duty Sel.
−
HD
ND
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
Hex
60
61
62
63
65
E2-11
(E4-11,
T1-02)
Motor rated power
kW
0.1
0.2
0.2
0.4
0.4
0.75 0.75
1.1
1.5
2.2
b3-06
Speed Search current 1
−
1.0
1.0
1.0
1.0
1.0
1.0
0.5
0.5
0.5
0.5
b8-04
Energy saving coefficient
−
481.7 356.9 356.9 288.2 288.2 223.7 223.7 196.6 169.4 156.8
C6-02
Carrier frequency
−
4
7
4
7
4
7
4
7
3
7
E2-01
(E4-01,
T1-04)
Motor rated current
A
0.6
1.1
1.1
1.9
1.9
3.3
3.3
4.9
6.2
8.5
E2-02
(E4-02)
Motor rated slip
Hz
2.5
2.6
2.6
2.9
2.9
2.5
2.5
2.6
2.6
2.9
E2-03
(E4-03)
Motor no-load current
A
0.4
0.8
0.8
1.2
1.2
1.8
1.8
2.3
2.8
3.0
E2-05
(E4-05)
Motor line-to-line
resistance
W
35.98 20.56 20.56 9.842 9.842 5.156 5.156 3.577 1.997 1.601
E2-06
(E4-06)
Motor leakage inductance
%
21.6
20.1
20.1
18.2
18.2
13.8
13.8
18.5
18.5
18.4
E2-10
(E4-10)
Motor Iron Loss
W
6
11
11
14
14
26
26
38
53
77
E5-01
Motor Code
hex
FFFF FFFF FFFF FFFF 0002 0002 0003 0003 0005 0005
L2-02
Momentary power loss
ride-through time
s
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.3
0.3
L2-03
Momentary power loss
Baseblock time
s
0.2
0.2
0.2
0.2
0.2
0.3
0.3
0.4
0.4
0.5
L2-04
Momentary power loss
voltage recovery time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
UV detection voltage
V dc
190
190
190
190
190
190
190
190
190
190
L3-24
Motor acceleration time
s
0.178 0.178 0.178 0.178 0.178 0.142 0.142 0.142 0.166 0.145
L8-02
Overheat alarm level
°
C
110
110
110
110
115
115
100
100
100
100
L8-09
Ground fault selection
−
0
0
0
0
0
0
0
0
0
0
L8-35
Installation Method Sel.
−
0
0
0
0
0
0
0
0
0
0
L8-38
Carrier frequency
reduction selection
−
1
1
1
1
1
1
1
1
1
1
n1-03
Hunting Prevention Time
Constant
ms
10
10
10
10
10
10
10
10
10
10
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...