A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
313
Para
me
te
r Lis
t
A
d3: Jump Frequency
Use d3 parameters to configure the drive Jump Frequency settings.
d3-01
Jump Frequency 1
d3-01 to d3-04 allow programming of three
prohibited frequency reference points for
eliminating problems with resonant vibration of
the motor / machine. This feature does not
eliminate the selected frequency values, but
accelerates and decelerates the motor through the
prohibited bandwidth.
The parameters must be according to the rule
d3-01
≥
d3-02
≥
d3-03.
0.0 to
400.0
0.0
Hz
A A A
294
d3-02
Jump Frequency 2
0.0
Hz
A A A
295
d3-03
Jump Frequency 3
0.0
Hz
A A A
296
d3-04
Jump Frequency
Width
This parameter sets the dead-band width around
each selected prohibited frequency reference
point. The bandwidth becomes the designated
Jump frequency, plus or minus d3-04.
0.0 to
20.0
1.0
Hz
A A A
297
d4: Frequency Reference Hold
Use d4 parameters to configure the drive frequency reference hold function.
d4-01
Frequency Reference
Hold Function
Selection
Determines if the frequency reference or
frequency reference bias is saved when the Run
command is removed or the power goes off.
0: Disabled
1: Enabled
This parameter is effective when the multi-
function inputs “Accel/Decel Ramp Hold”, “Up/
Down” or Up/Down 2”commands are selected
(H1-
= A or 10/11 or 75/76).
0,1
0
A A A
298
d4-03
Frequency Reference
Bias Step
(Up/Down 2)
Sets the bias added to the frequency reference
when the Up/Down 2 digital inputs are set.
When set to 0.00 Hz, the bias value is increased
or decreased according to d4-04.
When greater than 0.0 Hz, the bias value d4-03 is
added or subtracted to/from the frequency
reference. The acceleration or deceleration rate is
ultimately determined by d4-04.
0.00 to
99.99
Hz
0.00
Hz
A A A 2AA
d4-04
Frequency Reference
Bias Accel/Decel
(Up/Down 2)
Selects how the bias or frequency reference is
increased when using the Up/Down 2 function.
0: Use selected accel/decel time.
1: Use Accel/Decel Time 4 (C1-07 and C1-08).
0,1
0
A A A 2AB
No.
Name
Description
Range Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...