1.4 d: Reference Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
103
Pa
ra
m
et
er D
et
ai
ls
1
Figure 1.37
Figure 1.37 Up/Down 2 Example with Other Reference than Digital Operator and d4-01 = 1
Note:
Make sure to set the Up/Down 2 limits properly when using d4-01 = 1 in combination with the
Up/Down 2 function. Refer to
d4-08: Frequency Reference Bias Upper Limit (Up/Down 2) on
d4-09: Frequency Reference Bias Lower Limit (Up/Down 2) on page 106
for
details on the limit settings.
Clearing the Value that was Saved
Depending on which function is used, the frequency reference value that was saved can be
cleared by:
• releasing the acceleration hold input
• setting an Up or Down command while no Run command is active.
■
d4-03: Frequency Reference Bias Step (Up/Down 2)
Sets the bias that is added to or subtracted from the frequency reference by the Up/Down 2
function.
The operation depends on the set value:
Setting d4-03 = 0.0 Hz
While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased
using the accel/decel time determined by parameter d4-04.
No.
Parameter Name
Setting Range
Default
d4-03
Frequency Reference Bias Step
0.00 to 99.99 Hz
0.00 Hz
5 s
Bias
Output
frequency
Bias is saved in parameter d4-06
5 s
Up 2 command
d4-06 value