A.2 Parameter Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
363
Para
me
te
r Lis
t
A
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f
O
LV
P
M
T1-00
Motor Selection
1/2
Selects which set of motor parameters are used and
set during Auto-Tuning. If Motor 2 selection
(H1-
= 16) is not selected, this parameter will
not be displayed.
1: 1st Motor - E1 to E2
2: 2nd Motor - E3 to E4 (this selection is not
displayed if motor 2 has not been selected)
1, 2
1
A A
−
700
T1-01
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<54> The available tuning methods depend on control mode. Select values 2 or 3 in V/f Control, 0 or 2 in OLV control,
and 2 for Motor 2 control.
Auto-Tuning
Mode Selection
Selects the Auto-Tuning mode.
0: Rotational Auto-Tuning
2: Stationary Auto-Tuning for Line-to-Line
Resistance
3: Rotational Auto-Tuning for V/f Control
(necessary for Energy Savings and Speed
Estimation type Speed Search)
0, 2, 3
2 or 3
in V/f
0 or 2
in OLV
2 for
Motor 2
A A
−
701
T1-02
Motor Rated
Power
Sets the motor rated power in kilowatts (kW).
Note:
If motor power is given in horsepower, power
in kW can be calculated using the following
formula: kW = HP x 0.746.
0.00 to
650.00
A A
−
702
T1-03
Motor Rated
Voltage
Sets the motor rated voltage in volts (V).
0.0 to
255.5
200.0 V A A
−
703
T1-04
Motor Rated
Current
Sets the motor rated current in amperes (A).
10 to
200% of
drive
rated
current
A A
−
704
T1-05
Motor Base
Frequency
Sets the base frequency of the motor in Hertz (Hz).
0.0 to
400.0
60.0 Hz A A
−
705
T1-06
Number of
Motor Poles
Sets the number of motor poles.
2 to 48
4
A A
−
706
T1-07
Motor Base
Speed
Sets the base speed of the motor in revolutions per
minute r/min (RPM).
0 to
24000
1750
r/min
A A
−
707
T1-11
Motor Iron Loss
Provides the iron loss for determining the Energy
Saving coefficient.
The value set to E2-10 (motor iron loss) when the
power is cycled. If T1-02 is changed, an initial
value valid for the selected capacity will be shown.
0 to
65535
14W
A
− −
70B
These values differ
depending on the motor code
value and motor parameter
settings.