1.4 d: Reference Settings
100
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Figure 1.34
Figure 1.34 Jump Frequency Operation
Note:
1.
The drive will use the active accel/decel time to pass through the specified dead band range but will not
allow continuous operation in that range.
2.
When using more than one Jump frequency, make sure that d3-01 >= d3-02 >= d3-03.
◆
d4: Frequency Hold and Up/Down 2 Function
■
d4-01: Frequency Reference Hold Function Selection
This parameter is effective when either of the digital input functions listed below is used.
• Accel/decel ramp hold function (H1-
= A)
• Up/Down function (H1-
= 10 and 11, sets the frequency reference by digital inputs)
• Up/Down 2 function (H1-
= 75/76, adds a bias to the frequency reference using
digital inputs)
Parameter d4-01 determines whether or not the frequency reference or the frequency bias
(Up/Down 2) value is saved when the Run command is cleared or the power supply is shut
down.
The operation depends on what function parameter d4-01 is used with.
No.
Parameter Name
Setting Range
Default
d4-01
Frequency Reference Hold Function Selection
0 or 1
0
Output
frequency
Frequency
reference
Jump
Frequency
Width (d3-04)
Jump
Frequency 3
d3-03
Jump
Frequency 2
d3-02
Jump
Frequency 1
d3-01
Frequency
reference
decreases
Frequency
reference
increases
Jump
Frequency
Width (d3-04)
Jump
Frequency
Width (d3-04)
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...