2.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
285
ME
MOBUS/Mo
dbus
C
ommuni
cat
io
ns
2
◆
Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will
receive the message, but will not respond.
00D1H
CPF Contents 2
bit 0
Clock Fault (CPF16)
bit 1
Timing Fault (CPF17)
bit 2
Control Circuit Fault (CPF18)
bit 3
Control Circuit Fault (CPF19)
bit 4
Hardware fault at power up (CPF20)
bit 5
Hardware fault at communication start up (CPF21)
bit 6
A/D Conversion Fault (CPF22)
bit 7
PWM Feedback Fault (CPF23)
bit 8
Drive capacity signal fault (CPF24)
bit 9 to F
Reserved
00D8H
Option Card Fault Contents
bit 0
Option Compatibility Error (oFA00)
bit 1
Option not properly connected (oFA01)
bit 3
Option Self-diagnostics Error (oFA03)
bit 4
Option Flash Write Mode Error (oFA04)
bit 5 to F
Reserved
00FBH
Output current,
<1> Units are determined by parameter o1-03.
<2> 0.01 A units for drives set to 11 kW in Heavy or Normal Duty and 0.1 A units for drives set to 15 kW and above.
<3> The contents of a communication error are saved until the fault is reset.
<4> Depending on the motor used the correct motor pole number must be set to parameter E2-04, E4-04 or E5-05.
<5> For drive software version 1011 and later.
Register No.
Contents