2.9 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
281
ME
MOBUS/Mo
dbus
C
ommuni
cat
io
ns
2
00B0H
Option Code
Register contains ASCII code of 3rd and 4th digit of the option card type
number. Example: Register value is 5343H for “P3” if a SI-P3 option card
is installed.
00B5H
Frequency Reference
After Soft-starter
r/min units
00B6H
0.01% units
00B7H
Frequency Reference
r/min
00B8H
0.01% units
00BFH
oPE Error Number
00C0H
Fault contents 3
bit 0
Reserved
bit 1
Undervoltage (Uv1)
bit 2
Control Power Supply Undervoltage (Uv2)
bit 3
Soft Charge Circuit Fault (Uv3)
bit 4
Reserved
bit 5
Ground Fault (GF)
bit 6
Overcurrent (oC)
bit 7
Overvoltage (ov)
bit 8
Heatsink Overheat (oH)
bit 9
Heatsink Overheat (oH1)
bit A
Motor Overload (oL1)
bit B
Drive Overload (oL2)
bit C
Overtorque Detection 1 (oL3)
bit D
Overtorque Detection 2 (oL4)
bit E
Dynamic Braking Transistor Fault (rr)
bit F
Braking Resistor Overheat (rH)
00C1H
Fault contents 4
bit 0
External Fault at input terminal S3 (EF3)
bit 1
External Fault at input terminal S4 (EF4)
bit 2
External Fault at input terminal S5 (EF5)
bit 3
External Fault at input terminal S6 (EF6)
bit 4
Reserved
bit 5
Overspeed (oS)
bit 6
Excessive Speed Deviation (dEv)
bit 7
PG Disconnected (PGo)
bit 8
Input Phase Loss (PF)
bit 9
Output Phase Loss (LF)
bit A
Motor Overheat (PTC input) (oH3)
bit B
Digital Operator Connection Fault (oPr)
bit C
EEPROM Write Error (Err)
bit D
Motor Overheat Fault (PTC input) (oH4)
Register No.
Contents