1.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
133
Pa
ra
m
et
er D
et
ai
ls
1
■
F6-36: CANopen Communication Speed
Sets the communication speed for a CANopen option card if installed.
Settings:
■
F6-40: CompoNet Node ID
Selects the node ID of a CompoNet option board if installed.
■
F6-41: CompoNet Communication Speed
Sets the communication speed for a CompoNet option card if installed.
Settings:
■
F6-50: DeviceNet MAC Address
Sets the MAC address for a DeviceNet option card if installed.
No.
Parameter Name
Setting Range
Default
F6-36
CANopen Communication Speed
0 to 8
6
F6-36
Communication Speed
F6-36
Communication Speed
0
Auto detection
5
250 kbps
1
10 kbps
6
500 kbps
2
20 kbps
7
800 kbps
3
50 kbps
8
1 Mbps
4
125 kbps
No.
Parameter Name
Setting Range
Default
F6-40
CompoNet Node ID
0 to 63
0
No.
Parameter Name
Setting Range
Default
F6-41
CompoNet Communication Speed
0 to 255
0
F6-41
Communication Speed
F6-41
Communication Speed
0
93.75 kbps
3
3 Mbps
1
Reserved
4
4 Mbps
2
1.5 Mbps
5 - 255
Reserved