1.5 E: Motor Parameters
120
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 0: V/f Control
Setting 1: Open Loop Vector Control
■
E3-04 to E3-13
Parameters E3-04 through E3-14 set up the V/f pattern used for motor 2 like shown in
Figure 1.42
Figure 1.42 V/f Pattern for Motor 2
Note:
1.
The following condition must be true when setting up the V/f pattern: E3-09 =< E3-07 =< E3-06 <= E3-
11 <= E3-04
2.
To make the V/f pattern a straight line set E3-09 = E3-07. In this case the E3-08 setting is disregarded.
No.
Parameter Name
Setting Range
Default
E3-01
Motor 2 Control Mode Selection
0 or 2
0
No.
<1> Values shown here are for 200 V class drives. Double the value when using a 400 V class unit.
<2> Default setting is determined by the control mode for motor 2.
Parameter Name
Setting Range
Default
E3-04
Motor 2 Max Output Frequency
40.0 to 400.0 Hz
50.0 Hz
E3-05
Motor 2 Max Voltage
0.0 to 255.0
200.0 V
E3-06
Motor 2 Base Frequency
0.0 to 400.0
50.0 Hz
E3-07
Motor 2 Mid Output Frequency
0.0 to 400.0
E3-08
Motor 2 Mid Output Frequency Voltage
0.0 to 255.0
E3-09
Motor 2 Minimum Output Frequency
0.0 to 400.0
E3-10
Motor 2 Minimum Output Frequency Voltage
0.0 to 255.0
E3-11
Motor 2 Mid Output Frequency 2
0.0 to 400.0
0.0 Hz
E3-12
Motor 2 Mid Output Frequency Voltage 2
0.0 to 255.0
0.0 Vac
E3-13
Motor 2 Base Voltage
0.0 to 255.0
0.0 Vac
Output (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
E3-07 E3-06 E3-11 E3-04