1.1 A: Initialization
26
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 1: Water Supply Pump Application
Table 1.5 Water Supply Pump Parameters Settings
Table 1.6 Water Supply Pump: Preferred Parameters (A2-01 to A2-16)
Setting 2: Conveyor Application
Table 1.7 Conveyor: Parameter Settings
No.
Name
Optimum Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C1-01
Acceleration Time 1
1.0 s
C1-02
Deceleration Time 1
1.0 s
C6-01
Duty Rating
1: Normal Duty
E1-03
V/f Pattern Selection
0FH
E1-07
Mid Output Frequency
30.0
E1-08
Mid Output Frequency Voltage
50.0
L2-01
Momentary Power Loss Operation
Selection
1: Enabled
L3-04
Stall Prevention Selection during
Deceleration
1: Enabled
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection
E1-07
Mid Output Frequency
b1-02
Run Command Selection
E1-08
Mid Output Frequency Voltage
b1-04
Reverse Operation Selection
E2-01
Motor Rated Current
C1-01
Acceleration Time 1
H1-05
Multi-Function Digital Input Terminal
S5 Function Selection
C1-02
Deceleration Time 1
H1-06
Multi-Function Digital Input Terminal
S6 Function Selection
E1-03
V/f Pattern Selection
L5-01
Number of Auto Restart Attempts
No.
Parameter Name
Optimum Setting
A1-02
Control Method Selection
0: V/f Control
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Duty Rating
0: Heavy Duty