1.10 o: Operator Related Settings
1.10 o: Operator Related Settings
These parameters concern the various functions and features of the digital operator.
◆
o1: Display Settings and Selections
These parameters determine how data is shown on the operator display.
■
o1-01: Drive Mode Unit Monitor Selection
Selects which U -
monitor parameter will be displayed in the operation menu upon
power-up when o1-02 = 4. Press the up arrow key four times and select the desired monitor.
To select a monitor parameter, set the three numeric digits that make up that monitor. This is
done by entering the -
part of U -
. For a list of monitors, refer to
■
o1-02: User Monitor Selection After Power Up
Selects which monitor parameter will be displayed upon power up. Defaulted to show the
frequency reference when the drive is first turned on.
Setting 1: Frequency Reference (U1-01)
Setting 2: Forward / Reverse
Setting 3: Output Frequency (U1-02)
Setting 4: Output Current (U1-03)
Setting 5: User Selected Monitor (set by o1-01)
■
o1-03: Digital Operator Display Selection
Parameter o1-03 allows the programmer to change the units used in the following
parameters and monitors:
• U1-01: frequency reference
No.
<1> U2-
and U3-
parameters cannot be selected.
Name
Setting Range
Default
o1-01
Drive Mode Unit Monitor Selection
104 to 621
(U1-04 to U6-21)
106 (U1-06)
No.
Name
Setting Range
Default
o1-02
User Monitor Selection After Power Up
1 to 5
1