1.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
135
Pa
ra
m
et
er D
et
ai
ls
1
Setting 0: Disabled, No Fault Detection
Setting 1: Enabled
■
F6-56 to F6-61: DeviceNet Scaling Factors
These parameters define scaling factors for drive monitors in the DeviceNet Class ID 2AH -
AC/DC Drive Object.
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value x 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 50.0 and the scaling is set to F6-56 = 6, then
the value in the AC/DC Drive Object 2AH, Instance 1, Attribute 7 would be 500 x 2
6
=
32000.
■
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the
Heartbeat function.
No.
Parameter Name
Setting Range
Default
F6-54
<1> Valid from drive firmware version 1011 and later. Parameter number was F6-24 in older software.
DeviceNet Idle Mode Fault Detection
0 or 1
0
No.
Parameter Name
Setting Range
Default
F6-56
<1> Valid from drive firmware version 1011 and later.
DeviceNet Speed Scaling
-15 to 15
0
F6-57
DeviceNet Current Scaling
-15 to 15
0
F6-58
DeviceNet Torque Scaling
-15 to 15
0
F6-59
DeviceNet Power Scaling
-15 to 15
0
F6-60
DeviceNet Voltage Scaling
-15 to 15
0
F6-61
DeviceNet Time Scaling
-15 to 15
0
No.
Parameter Name
Setting Range
Default
F6-56
<1> Valid from drive firmware version 1011 and later.
DeviceNet Heartbeat
0 to 10
0