1.7 H: Terminal Functions
140
YASKAWA ELECTRIC
SIEP C710606 10A YASKAWA AC Drive - V1000 PRELIM. Programming Manual
Setting 0: 3-Wire Sequence
When one of the digital inputs is programmed for 3-wire control, that input becomes a
forward/reverse directional input, S1 becomes the Run command input, and S2 becomes the
Stop command input.
The drive will start the motor when the Run input S1 is closed for longer than 50ms. The
drive will stop the operation when the Stop input S2 is released for a brief moment.
Whenever the input programmed for 3-wire sequence is open, the drive will be set for
forward direction. If the input is closed, the drive is set for reverse direction.
Note:
When 3-wire sequence is selected the Run and Stop command must be input at S1 and S2.
Figure 1.44
Figure 1.44 3-Wire Sequence Wiring Diagram
10
Up Command
65
KEB Ride-Thru 1 (N.C.)
11
Down Command
66
KEB Ride-Thru 1 (N.O.)
12
Forward Jog
67
Communications Test Mode
13
Reverse Jog
68
High-Slip Braking
14
Fault Reset
6A
Drive Enable
15
Fast-Stop (N.O.)
75
Up 2 Command
16
Motor 2 Selection
76
Down 2 Command
17
Fast-stop (N.C.)
7A
KEB Ride-Thru 2 (N.C.)
18
Timer Function Input
7B
KEB Ride-Thru 2 (N.O.)
19
PID Disable
7C
Short-Circuit Braking (N.O.)
1A
Accel/Decel Time Selection 2
7D
Short-Circuit Braking (N.C.)
1B
Program Lockout
7E
Forward/Reverse Detection (V/f
Control with Simple PG Feedback)
1E
Reference Sample Hold
7F
Bi-directional PID output enable
20 to 2F External Fault
90 to 96 FBD’s Digital Input 1 to 7
30
PID Integral Reset
9F
FBD’s Disable
Setting
Function
Page
Setting
Function
Page
S1
S2
S5
SC
Run command (runs when closed)
Drive
Stop switch
(N.C.)
Run switch
(N.O.)
Stop command (stops when open)
FWD/REV (Multi-function input)
(H1-05 = 0)
Sequence Input Common
Summary of Contents for OYMC V1000
Page 2: ...2 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual...
Page 8: ...8 YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual INDEX 393...
Page 407: ...YASKAWA ELECTRIC SIEP C710606 10A YASKAWA AC Drive V1000 PRELIM Programming Manual 407...